Availability: | |
---|---|
Quantity: | |
Features
■ Safe:
• Early thermal runaway prewarning and PACK-level combustible gas detection to realize targeted fire extinguishing by coordinating with BMS and EMS;
• Using flame retardant material and multiple ESS can be connected seamlessly, saving 20% of space and reducing maintenance cost by 10%;
« Patented bionic tree runner design with PACK temperature difference 彡5OC and battery cycle life increased by 12%;
• Adopt "emergency avoidance design" with BMS and EMS online backup to reduce failure rate by 5%;
• Compact and safe design with core components (air conditioners, PCS) integrated within the cabinet to reduce the risk of hidden failure.
■ Simple:
- All-in-one design and modular installation with single cabinet covering an area of just1.68m2;
• Applicable to multiple industrial scenarios and easy to connect to the grid;
• Easily plug and play with aviation plug and simple capacity expansion covering power range from
50kW to 1MW;
• Factory prefabrication and integrated
transportation to reduce the transportation,
installation and commissioning fees by 15%.
■ Smart:
• Remote cloud operation and maintenance, supporting remote and local monitoring;
• Smart balancing strategy and system AI prewarning to ensure the consistency of battery life cycle;
• Support black start function with reliable power supply in off-grid/micro-grid mode;
• Support a variety of operation modes (virtual power plant, grid-connected, off-grid) to improve revenue.
Technical Parameters
Model | Ener HexonM Smart215 | |
Battery | Cell type | LFP-3.2V-280Ah |
Rated capacity[kWh] | 215.04 | |
Charge and discharge ratio | ≤0.5CP | |
Voltage range[V | 672~864 | |
AC Parameters | Rated power[kW] | 100 |
Rated grid voltage[V] | 400 | |
Voltage range[V | 320~460 | |
Rated current[A] | 144 | |
Rated grid frequency [Hz] | 50/60 | |
Grid frequency range[Hz] | 45~55/55~65 | |
Distortion rate of total | <3%(Rated power) | |
Power factor | >0.99(Rated power) | |
Powerfactor adjustable range | -1(ahead)~1(lag) | |
AC Parameters | AC off-grid voltage[V] | 400 |
AC off-grid frequency[Hz] | 50/60 | |
AC voltage range | 十3% | |
Off-grid outputvoltage | <3%(Linear load) | |
System | BMS | Level2 |
Dimension[mm](L*W*H) | 1200*1400*2200 | |
Weight[kg] | 2300 | |
Ingress protection | IP54 | |
Operating temperature range | -30~+50℃(>45℃ derating) | |
Operating humidity range | 0~95%(no condensastion) | |
Auxiliary electrical parameter | 6kW-380V/50Hz | |
Fire protection system | Type S aerosol/HFC-propane/perfluorohexanone | |
Installation mode | outdoor installation | |
Anticorrosive level | C3(C4\C5 optional) | |
Altitude | Within 3000m | |
Working condition | Max.2 charge and 2 discharge per day | |
System communication interface | Ethernet、RS485 | |
External system | Modbus TCP、 | |
Certificate | GB/T36276、 |