Utility Scale Battery Energy Storage Systems Offering Energy Storage Solutions in a 20 Foot High Cube Container with Liquid Cooling
20ft container battery storage
,liquid-cooled battery energy storage
,utility scale energy storage system
UTILITY-SCALE DC BATTERY STORAGE
6.26 MWh Liquid-Cooled Battery Storage in a 20 ft Container
YT-Container ESS-6.26MWh provides a 6.26 MWh LFP battery block with 1.56 MW rated DC charge and discharge power. The 1500 V class system combines 392 Ah cells, three-level battery management and liquid cooling within a standard 20-foot high-cube enclosure. It is intended for integration into utility storage plants, renewable-energy projects and specifically engineered microgrids.
Equipment and Supply Scope
The listed equipment is a DC-side battery container. The specified configuration includes the battery modules and racks, battery protection units, DC protection, system BMS, thermal management, monitoring and the stated fire-protection functions. A compatible bidirectional PCS, project EMS/SCADA, transformer, switching and grid-connection equipment are external integration items unless separately included in the agreed scope.
YINTU is an energy storage solution provider. We work with manufacturing partners to match battery equipment with project requirements, coordinate technical interfaces and define the supply boundary. The container rating does not by itself establish a complete AC plant output, grid-service qualification or site backup performance.
Value in Utility and Renewable-Energy Projects
Solar and wind energy time shifting
Store selected renewable generation when production exceeds the desired delivery schedule, then discharge through the chosen PCS when energy is needed later. The battery block provides energy capacity for this operating plan. Renewable output, charging availability, export limits and auxiliary demand determine how much energy can actually be shifted.
Defined battery blocks for larger storage plants
The 20-foot format gives project designers a repeatable DC battery building block. Plant power and energy can be assessed separately by selecting the number of containers and the compatible conversion equipment. At the stated nameplate ratings, 6.26 MWh divided by 1.56 MW is approximately four hours. Delivered AC duration depends on usable SOC, losses, auxiliaries, aging and the agreed dispatch conditions.
Peak management and controlled grid exchange
A project EMS can coordinate battery dispatch around defined grid-demand peaks or an operating schedule. Useful peak support requires both sufficient converter power and usable energy over the relevant period. The design should also include reserve allocation and recovery between repeated peaks. Any savings or infrastructure-deferral assessment must use the actual connection and operating profile.
Engineered microgrids, reserves and critical-load supply
The container can form the battery section of a specifically engineered microgrid or backup system. Island operation, black start and grid-support functions depend on a suitable PCS, controls, switching, protection and operating sequence. Frequency-response performance or grid-forming capability is not guaranteed by the DC enclosure alone.
Battery Architecture and System Integration
The source configuration contains 4,992 LFP cells. Each 1P104S module is rated at 130.45 kWh and 332.8 V. Four modules form a 1P416S rack, rated at 521.8 kWh and 1331.2 V. Twelve racks in parallel form the 12P416S system. Six BPUs provide the specified circuit protection and rack-management functions, while the electrical cabin houses DC protection, system BMS and a 3 kVA UPS.
Match the external PCS to the complete 1123.2-1497.6 Vdc operating window and the 1.56 MW rated charge/discharge power, including the intended current limits and communications. The PCS converts DC battery power to and from the AC system. Project EMS/SCADA supervises dispatch while the BMS supplies battery limits and protection information. The electrical-cabin UPS rating does not define an AC backup supply for site loads.
Technical Specifications
DC electrical ratings
| Parameter | Specification |
|---|---|
| Model | YT-Container ESS-6.26MWh |
| Rated battery energy | 6.26 MWh |
| Rated DC charge / discharge power | 1.56 MW / 1.56 MW (0.25P) |
| Rated DC voltage | 1331.2 Vdc |
| DC operating voltage | 1123.2-1497.6 Vdc |
| Rated capacity / configuration | 4704 Ah / 12P416S |
| Cell chemistry / capacity / voltage | LFP / 392 Ah / 3.2 V |
| Source-rated round-trip efficiency | ≥95% at 0.25P |
| Cell cycle life | ≥8,000 cycles under the source test conditions |
RTE is a source-rated value at 0.25P. Delivered AC efficiency also depends on the selected PCS, auxiliary consumption and operating conditions. Cell-life conditions are 25 ±2°C, 0.25P charge/discharge and 70% end-of-life capacity. This cell-level result is not a system warranty term.
Configuration, thermal management and auxiliaries
| Parameter | Specification |
|---|---|
| Cells | 4,992 x 392 Ah LFP cells |
| Battery modules | 48 x 1P104S; 130.45 kWh / 332.8 V each |
| Battery racks / clusters | 12 x 1P416S; 521.8 kWh / 1331.2 V each |
| Battery protection units | 6 BPUs |
| Electrical cabin / UPS | 1 cabin with DC protection, system BMS and 3 kVA UPS |
| Liquid-cooling equipment | 30 kW cooling / 12 kW heating capacity |
| Coolant / chiller supply | 50% glycol solution / 380-415 Vac, 3N~, 50 Hz |
| Electrical-cabin air conditioner | 1 kW cooling; 230 Vac ±15%, 50 Hz |
| Battery-cabin dehumidifier | 7 L/day at 35°C, 95% RH; 220 Vac, 50/60 Hz |
Cooling and heating capacities describe thermal performance rather than the chiller’s electrical input demand. The chiller and electrical-cabin air conditioner are specified for 50 Hz. Confirm auxiliary-supply compatibility for the destination project and include auxiliary energy in the plant operating model.
Enclosure and environment
| Parameter | Specification |
|---|---|
| Container format | 20-foot high-cube container |
| Dimensions (L x W x H) | 6058 x 2438 x 2896 mm (±10 mm) |
| Weight | 46 t ±1 t |
| Container / module / BPU protection | IP55 / IP67 / IP65 |
| Enclosure corrosion / impact | C4 / IK10 |
| Operating ambient temperature | -20 to +50°C |
| Storage temperature | -30 to +55°C |
| Relative humidity | 0-95%, non-condensing |
| Operating altitude | ≤3000 m; derating above 3000 m as stated in source |
Controls and layered protection
| Parameter | Specification |
|---|---|
| BMS architecture | Module BMS + Rack BMS + System BMS |
| Communication | RS485 / Ethernet / CAN 2.0 |
| Cell balancing | Passive balancing, 100 mA |
| Electrical protection | Short circuit, overcharge, overdischarge, overtemperature, surge protection and emergency stop |
| Monitoring | Temperature, humidity, CO, H₂ and water ingress |
| Fire protection | Condensed aerosol suppression and water fire protection |
| Detection and alarms | Smoke / heat detection and audible / visual alarms |
| Ventilation and pressure management | Explosion-proof exhaust and pressure relief |
The safety configuration combines battery monitoring, protective control and the listed suppression functions. Final fire-system design, interfaces and installation requirements must match the supplied configuration and the site. No single protection feature substitutes for a complete project design.
Referenced Standards and Documentation
The source lists UL 1973, UL 9540, UL 9540A, IEC 62619, IEC 63056, IEC 62933-5-2 and IEC 62933-2-1 as battery/system references. It also lists UN 38.3 and UN 3536 for transport, and IEC 60529 (IP55), NFPA 855/68/69, NFPA 70E and GR-63-CORE Zone 4 as enclosure or installation references. Applicable certificates, test reports and model coverage must be confirmed for the offered configuration. A reference list is not a claim that every certification has been issued for every supplied model.
Site Planning and Project Scope
- Define required AC power, usable energy, delivery duration and reserve commitments from the project duty.
- Review the PCS voltage window, battery limits, control interfaces and agreed grid functions.
- Confirm auxiliary supplies, climate, corrosion conditions, foundation loading and emergency access.
- Plan transport, lifting and securing for 46 t ±1 t. The source requires maintenance access on both sides and the end.
- Agree battery, PCS, EMS, transformer, switchgear, installation and commissioning responsibilities before ordering.
Frequently Asked Questions
Does this listing include the PCS or direct PV input?
The listed equipment is the DC battery container. PCS, project EMS and grid-connection equipment are external integration items. PV integration requires the appropriate PV conversion architecture and plant controls. Direct connection of PV strings to the battery enclosure is not specified.
Is this a guaranteed four-hour AC system?
Approximately four hours is the ratio of the nameplate energy to the rated DC power. The usable AC duration depends on SOC limits, conversion and auxiliary losses, temperature, aging and reserve settings. Agree the required delivery test and end-of-life criteria for the project.
Does ≥8,000 cycles establish the product warranty?
It is a cell-level test reference under the stated temperature, charge/discharge rate and remaining-capacity conditions. Warranty duration, throughput, operating limits and system performance commitments require a separate written agreement.
Can the container provide frequency response or off-grid power?
Those are functions of a complete engineered system. They require compatible PCS controls, the necessary power and energy reserve, metering, protection and any applicable connection or service approvals. They cannot be confirmed from the battery enclosure rating alone.
Discuss Your Utility Storage Project with YINTU
Share required AC power and usable energy, the renewable-generation or load profile, grid voltage, operating schedule, site climate and available layout. YINTU can coordinate battery selection, PCS matching and technical clarification with manufacturing partners for a defined supply scope.
For related planning topics, read our PCS control-mode guide and air-cooled versus liquid-cooled BESS guide.
Data are based on the supplied YT-Container ESS-6.26MWh datasheet, V1.0, October 2026, which references a Rev.3 technical specification. Final scope, drawings, operating limits and documentation follow the agreed project configuration. Images show a product rendering and application concepts.