Integrated 100 KWh Energy Storage Cabinet Hybrid ESS For Commercial And Industrial

Brand Name:YINTU
Model Number:YT-Hybrid ESS-55kW-100kWh
Price:Quotation on request
Product Details
Highlight:

100 kWh Commercial Industrial Hybrid ESS

,

Integrated 100 KWh Energy Storage Cabinet

Battery Chemistry: LiFePO4
Rated Battery Energy: 100 KWh
Rated AC Power: 55 KW
AC Voltage: 400/230 V AC, Three Phase
AC Connection: L1/L2/L3/N/PE
Rated Frequency: 50/60 Hz
Maximum AC Current: 80 A
Maximum PV Power: 75 KW
Maximum PV Voltage: 850 V DC
MPPT Voltage Range: 200-800 V DC
Maximum PV Input Current: 60 A + 60 A
MPPT Channels: 2
Switching Time: <10 Ms
Generator Interface: Yes
Communication: RS485/WiFi
Cabinet Protection: IP54
Battery Cooling: Air Conditioner
Operating Temperature: -10 To +50 C
Dimensions (Source Order): 740 × 1,348 × 2,280 Mm
Approximate Weight: Approx. 1,200 Kg
Product Description

COMMERCIAL & INDUSTRIAL ENERGY STORAGE SOLUTIONS

100 kWh / 55 kW Hybrid Storage for Commercial Sites and Estates

An integrated 100 kWh storage cabinet for small commercial solar projects, rural hospitality and estate energy management. The system combines a LiFePO4 battery, PCS, BMS, EMS, two MPPT channels and a diesel generator interface. It supports grid-connected and off-grid applications at 400/230 V AC, 50/60 Hz.

Equipment Overview

The cabinet integrates 100 kWh rated battery energy, 55 kW rated AC power, up to 75 kW PV input, battery air conditioning, intelligent PCS cooling and integrated fire protection. External PV modules, generator equipment, distribution, protection and installation works are defined separately in the project scope.

YINTU is an energy storage solution provider. We combine project requirements with products from capable manufacturing partners, coordinating equipment selection, system interfaces and technical documentation for the customer and local installation team.

YT-Hybrid ESS-55kW-100kWh application concept
Illustrative application concept, not a completed project reference. Equipment and site layout depend on the project.

Small Business and Large Estate Applications

Boutique hotels and country guesthouses

Use available rooftop solar across daytime services and selected evening loads. Divide essential reception, communications and refrigeration circuits from discretionary heating and comfort loads when planning backup.

Food retail and small processing sites

Plan battery operation around refrigeration, packaging and operating hours. Temperature-sensitive stock requires a complete continuity plan; battery capacity alone does not establish acceptable outage duration.

Large estates with substantial rooftop PV

Integrate PV arrays from suitable buildings into a coordinated energy plan with 100 kWh nominal battery storage. The 55 kW rated output must be checked against coincident household, pump and service-building demand.

Small factories and light workshops

Use recorded demand and production schedules to evaluate solar self-consumption and peak management. Coordinate motor starts and phase loading with the supplier rather than assuming the cabinet can support any industrial load.

Rural businesses with diesel backup

Combine the specified generator interface with battery reserve and solar generation. YINTU helps clarify the equipment interfaces; a local design team confirms the generator controls, protection and approved operating sequence.

System Features and Project Value

Solar and storage in one cabinet

Two MPPT channels support a specified maximum PV input of 75 kW. PV string design must respect the 850 V DC maximum voltage, 200–800 V DC MPPT range and 60 A + 60 A maximum input current; PV nameplate power is not battery discharge power.

Capacity selected around the operating plan

The 100 kWh rating describes nominal battery energy. Usable AC energy and runtime depend on discharge limits, conversion losses, auxiliary consumption, temperature and the reserve policy. Load measurements are required for a meaningful backup estimate.

Three-phase grid and off-grid operation

The specified connection is L1/L2/L3/N/PE at 400/230 V AC. Grid-connected and off-grid rated powers are the same for each configuration. Confirm phase balance, starting loads, local connection rules and protection coordination.

Generator coordination and transfer

A diesel generator port is specified, with a grid/off-grid switching time below 10 ms. Transfer performance depends on configuration and load requirements; this is not an unconditional no-break guarantee for every appliance or IT load. Generator ratings and control details require confirmation.

Cabinet environment and monitoring

IP54 cabinet protection, battery air conditioning, intelligent PCS cooling and integrated fire protection support the equipment design. RS485/WiFi communication is specified. Installation location, drainage, foundation, clearance and access must follow the approved project documents.

How the System Fits Your Site

PV connects to the integrated MPPT inputs. The 100 kWh battery and PCS manage energy within the cabinet, while the AC connection serves selected three-phase business or estate loads. Grid and diesel generator interfaces must use the approved isolation, protection and control arrangement. The diagram is a functional overview, not installation wiring or permission to parallel sources. Export, zero-export and generator operating modes must be confirmed for the project.

YT-Hybrid ESS-55kW-100kWh conceptual system topology
Concept diagram only. Follow the approved single-line diagram and installation documents.

Technical Specifications

Battery and Configuration

Parameter Specification
Battery chemistry LiFePO4
Rated battery energy 100 kWh
Rated AC power (grid-connected) 55 kW
Rated AC power (off-grid) 55 kW
Maximum AC current (grid/off-grid) 80 A
Source configuration reference B100-55H3-75M2-HX1

PV Input

Parameter Specification
Maximum PV power 75 kW
Maximum PV voltage 850 V DC
MPPT voltage range 200–800 V DC
Maximum PV input current 60 A + 60 A
MPPT channels 2

AC and Operating Interfaces

Parameter Specification
AC voltage / connection 400 / 230 V AC; L1/L2/L3/N/PE
Rated frequency 50 / 60 Hz
Grid / off-grid switching time <10 ms
Maximum parallel units 3 (listed in off-grid section; subject to approved system design)
Diesel generator port Yes
Communication RS485 / WiFi

Cabinet and Environment

Parameter Specification
Cabinet ingress protection IP54
Fire protection system Integrated
Operating temperature −10 to +50°C
Relative humidity 5–95%
Altitude <3,000 m
Battery cooling Air conditioner
PCS cooling Intelligent cooling
Dimensions (source order) 740 × 1,348 × 2,280 mm
Weight Approx. 1,200 kg

From Site Requirements to a Storage Solution

1. Define the operating objective

Identify whether the priority is peak management, solar self-consumption, backup or microgrid operation. Use the actual load profile and generation resources to set the power, energy and operating reserve.

2. Match equipment and interfaces

YINTU coordinates equipment selection and technical clarification with the manufacturing partner, including voltage, controls, environment, expansion and optional functions.

3. Confirm delivery and service scope

Confirm the cabinet configuration, PV string design, grid requirements, generator controls, protection, earthing, installation clearances and commissioning responsibilities before ordering. YINTU coordinates the technical scope with the manufacturing partner; local qualified professionals complete the approved installation. Warranty, certification documents, lead time and after-sales arrangements are confirmed in the project quotation.

Frequently Asked Questions

Is this suitable for a large home or estate?

It can be considered for a property with a suitable three-phase electrical system and a professionally designed installation. A site survey must confirm voltage, phase balance, peak demand, motor starting and backup circuits. It is not a plug-in appliance for an ordinary single-phase household.

How long will the battery power the site?

The nominal 100 kWh battery rating does not define a fixed runtime. Share the critical-load profile and required reserve so the usable energy, losses and operating limits can be assessed. Entire-site backup must not be assumed.

Can existing PV and a diesel generator be used?

Possibly, after checking the PV electrical design and existing inverter architecture, as well as generator interface and control compatibility. The built-in PV input and generator port do not remove the need for a site-specific integration design.

Can more cabinets be connected?

The datasheet lists a maximum of three parallel units in the off-grid section. Confirm the approved configuration, controls and protection with the supplier; parallel capability in every operating mode is not implied.

Does YINTU manufacture this cabinet?

YINTU provides energy storage solutions using products from manufacturing partners. We help clarify requirements, select the appropriate equipment and coordinate technical and delivery arrangements. Project certification, warranty and service scope are confirmed before ordering.

Plan Your Business or Estate Energy System

Share your location, three-phase supply details, daily load profile, maximum demand, PV capacity, generator information and preferred backup loads. For estates, include the main residence, guesthouses, pumps, cooling and EV charging schedules. YINTU will help match battery capacity and power configuration to the operating plan.

Specifications are transcribed from the supplied YINTU datasheet, version 1.0 (2026.10). Dimensions follow the source order. Images are illustrative and configuration may vary. Final equipment, interfaces and operating limits are subject to the confirmed technical agreement. Nominal battery energy is not usable AC energy or a guaranteed backup duration.

You May Also Like
Quality Floor Standing Residential Energy Storage Systems 16 KWh Long Lasting Home Energy Solutions factory

Floor Standing Residential Energy Storage Systems 16 KWh Long Lasting Home Energy Solutions

A 16 kWh floor-standing LiFePO4 battery with 51.2 V, 314 Ah and four casters. Standard current: 100 A; maximum continuous current: 200 A. Supports up to 15 parallel units, Bluetooth and BMS communication with a compatible external inverter.
Quality Indoor Floor Standing Residential Energy Storage Systems All In One Solar Storage For Homes factory

Indoor Floor Standing Residential Energy Storage Systems All In One Solar Storage For Homes

Floor-standing home solar storage with an integrated off-grid PV inverter and LiFePO4 battery. Four configurations offer 5.12–14.3 kWh and 5–11 kW, with direct PV input, AC charging and 230 V output. IP20 for indoor use.
Quality 12 KW / 32 KWh Stackable Home Solar Energy Storage Systems All In One ESS IP20 factory

12 KW / 32 KWh Stackable Home Solar Energy Storage Systems All In One ESS IP20

A 32 kWh stackable home ESS using 2 × 16 kWh battery modules and a 12 kW split-phase inverter. The appliance-style design combines solar input and battery storage for compatible 120 / 240 V homes.
Quality 5 KW 10.24 KWh Stackable Residential Battery Storage Systems All In One Solar ESS factory

5 KW 10.24 KWh Stackable Residential Battery Storage Systems All In One Solar ESS

A 10.24 kWh stackable home battery with an integrated 5 kW inverter, 120 V AC output and up to 6 kW PV input. The appliance-style enclosure brings solar charging and battery storage into a tidy indoor system.
Contact Us