125 kW / 261 kWh Hybrid ESS for Existing Commercial PV Sites
125 kW hybrid ESS
,261 kWh commercial ESS
,ESS for existing PV sites
YINTU ENERGY STORAGE SOLUTIONS
125 kW / 261 kWh Hybrid ESS for Existing Commercial PV Sites
A retrofit planning configuration for commercial sites with existing solar equipment. Review AC and DC interfaces, export metering and backup separation before selecting the hybrid cabinet.
YINTU is an energy storage solution provider working with capable manufacturing partners. We coordinate configuration selection and technical interfaces for the customer’s project.
Selected equipment and configuration
| Parameter | Specification |
|---|---|
| Model | YT-Hybrid ESS-125kW-261kWh |
| Selected configuration | 125 kW / 261 kWh |
| Source model reference | IYP-B261L-125H3-120M1-HX1 |
| Integrated PV input | 120 kW maximum |
| PV voltage | 250-850 Vdc MPPT, 950 Vdc maximum |
| AC connection | 400 / 230 V, three phase, 50 / 60 Hz |
| Battery cooling | Liquid cooling |
Retrofit objective
This application is for a commercial site that already has grid-connected PV and wants to add storage without redesigning the entire power supply. First map the existing PV inverter, meter, transformer and essential-load circuits. The 125 kW cabinet integrates LFP storage, PCS, BMS, EMS and a direct PV input, with a generator port available in the source configuration.
Choose the integration route
If the existing PV inverter stays on the grid-side AC bus, meter both PV production and grid exchange so the storage dispatch responds to the actual site balance. Export limitation needs a defined meter location, communication path and control settings. If selected arrays are to move to the cabinet’s DC input, check string voltage, current, isolation, earthing and the manufacturer-approved PV configuration. Confirm the MPPT option in the final order.
Backup boundary
An existing grid-following PV inverter may stop when the grid fails. Any requirement to operate that inverter on an islanded bus needs specific compatibility and protection approval. Establish which loads the cabinet serves, the isolation sequence, neutral arrangement and generator coordination on the single-line diagram. The source’s switching value is a component specification and must be validated with the installed loads.
YINTU project review
YINTU works with manufacturing partners to select equipment and coordinate the retrofit interfaces. Send the existing single-line diagram, inverter model and firmware, PV string schedule, interval loads and export permission. The quotation should identify supplied cabinet hardware, metering, transfer equipment, installation and commissioning responsibilities.
Explore Commercial & Industrial Energy Storage for related YINTU equipment options.
Product rendering. Values are based on the supplied model datasheet. Confirm final equipment, configuration, interfaces and operating limits in the project documentation.