50 kW Solution115 ESS for Essential-Load Energy Reserve
50 kW ESS essential-load reserve
,Commercial industrial energy storage
,115 ESS essential-load backup
YINTU ENERGY STORAGE SOLUTIONS
50 kW Solution115 ESS for Essential-Load Energy Reserve
A Solution115 application that protects an energy reserve for defined essential circuits while using the remaining battery window for daily commercial energy management.
YINTU is an energy storage solution provider working with capable manufacturing partners. We coordinate configuration selection and technical interfaces for the customer’s project.
Selected equipment and configuration
| Parameter | Specification |
|---|---|
| Model | YT-DS5T0115-P0050A |
| Manufacturer series | Ener Hexon Solution115 |
| Rated converter power | 50 kW |
| Rated battery energy | 115.2 kWh |
| Nominal battery voltage | 768 V |
| Included systems | Converter, BMS, EMS and STS |
| Enclosure dimensions (W x D x H) | 1150 x 1100 x 2050 mm |
Reserve-led application
Use this operating approach at a small commercial facility where selected controls, communications, access systems or other essential circuits need a protected battery reserve. The cabinet combines 50 kW conversion with 115.2 kWh nominal energy. Build the reserve around a defined circuit list and interruption requirement rather than the facility’s total connected load.
Calculate the shared energy budget
A 20 kW essential load running for 2 hours needs 40 kWh delivered to the circuits. Establish the battery energy allocation after allowing for inverter and auxiliary losses, the permitted SOC window and aging. Daily tariff dispatch should use the energy above that protected allocation. If the required reserve and daily dispatch overlap, reduce discretionary discharge or change the equipment configuration.
Transfer and load acceptance
The manufacturer identifies integrated STS but does not specify a universal transfer time in this source. Confirm the intended switching sequence and verify it with the actual loads. Keep motor starting, phase imbalance, protection coordination and neutral arrangements in the acceptance plan. Existing PV connected through its own inverter requires separate island-mode compatibility review.
YINTU supply coordination
YINTU is the solution provider and coordinates YOTAI equipment selection, reserve settings and project interfaces. Specify essential-load distribution, metering, external PV inverter, installation and commissioning responsibilities in the quotation. The reserve calculation is a project design exercise and should use measured load data and the agreed operating limits.
Explore Commercial & Industrial Energy Storage for related YINTU equipment options.
Product rendering. Values are based on the supplied model datasheet. Confirm final equipment, configuration, interfaces and operating limits in the project documentation.