20-Foot 5.016 MWh DC Battery Container for Service-Aisle Layouts
20-foot 5.016 MWh battery container
,DC battery container service-aisle layout
,utility scale battery energy storage
20-Foot 5.016 MWh DC Battery Container for Service-Aisle Layouts
Plan a 5,015.96 kWh non-walk-in battery container around external service access. Check cable routes, liquid-cooling service zones and the separately selected PCS and plant controls.
YT-Utility ESS-5015kWh
Selected configuration
| Rated DC battery energy | 5015.96 kWh |
|---|---|
| Cell chemistry / capacity | LFP, 314 Ah |
| Nominal DC voltage / window | 1331.2 V / 1164.8–1497.6 V |
| Container dimensions | 6058 × 2438 × 2896 mm, 20 ft high cube |
| Approximate mass | 41 t |
| Cooling / enclosure | Water-glycol liquid cooling, IP55 |
| Auxiliary supply | Approx. 40 kW, 400 V / 50 Hz, 3N + PE |
| Maintenance / communications | Outdoor external maintenance, Modbus TCP over agreed interfaces |
Draw the service aisle before setting row spacing
The Aurora 5015 is a non-walk-in 20-foot high-cube DC battery block. Its 6058 × 2438 × 2896 mm enclosure is one part of the installed envelope. Use the manufacturer’s arrangement to identify the external door and panel openings, required removal space and liquid-cooling service points. Reserve a clear route for maintenance handling and emergency access. Coordinate the row orientation and spacing with civil and site protection requirements.
Separate the cable, service and lifting paths
Map the DC cable routing from the container to the selected PCS and coordinate crossing points with service access, barriers and drainage. Use the approximately 41 t source mass for preliminary logistics screening and obtain the verified shipping and lifting data for the ordered unit. Confirm the foundation and equipment clearance requirements from the approved drawings before placing multiple blocks.
Set the site integration and service responsibilities
The DC operating range is 1164.8–1497.6 V. Review the PCS voltage window, battery current limits, control handshake, fault isolation and maintenance procedures for the proposed arrangement. Agree the BMS data exchange with the plant EMS. The source lists an approximate 40 kW auxiliary supply at 400 V, 50 Hz. Confirm the selected auxiliaries, feeder characteristics and coordination with the site service supply.
Coordinate the DC battery and the external plant package
YINTU is an energy storage solution provider. We coordinate the battery container and its mechanical and electrical interfaces with the manufacturing partner. The PCS, plant EMS, transformer, switchgear and connection equipment are separate project packages. Confirm the final duty and equipment scope with the project team, including the applicable power limits for the chosen DC-to-AC arrangement.
Equipment illustration based on the existing model cover. The final service envelope and supply boundary follow the technical agreement.
Floor Standing Residential Energy Storage Systems 16 KWh Long Lasting Home Energy Solutions
Indoor Floor Standing Residential Energy Storage Systems All In One Solar Storage For Homes
12 KW / 32 KWh Stackable Home Solar Energy Storage Systems All In One ESS IP20