Availability: | |
---|---|
Quantity: | |
Features
Safe:
·PACK level+container-level millisecond level sensing to achieve targeted fire extinguishing;gas firefighting+
·water firefighting to prevent re-ignition;active exhaust +third-level explosion venting to prevent secondarydamage;
·Three-level thermalinsulation for cells,PACK,and clusters,with fire resistancetime more than 2 hours;
·PACK,cluster,heap and system four-level fuse protection mechanism,reducingsecurity risks by 30%;
·5VA-level new flame-retardantinsulation material,flame-retardant capability increased by 25%.
Simple:
·314Ah battery,extremely narrow cold plate,standard 20-foot HQ container nominal energy 5.015MWh,coveredarea<15m²,better EPC cost;
·String architecture,AC side coupling,avoidsinter-cluster circulation,and increases available power by9%;
·The entire container is factory prefabricated,installed,and debugged,and the project delivery time isshortened by50%.
Smart:
·Battery core temperature difference isless than 2.5℃,AI model predicts remaining life and battery core safetyrisks,guides preventive maintenance,and increases battery life by12%;
·Active lossless equalization,self-healing and self-balancing,single-cluster automatic switching control,eliminatingthe need forexpert on-site maintenance;
·Intelligent debugdetection system to predict error early.
Technical Parameters
Type | Name | Parameters | Remarks | |
Battery | Cell type | LFP-3.2V-314Ah | ||
Rated capacity[kWh] | 5015.96 | P2,@25℃±3℃ | ||
Nominal voltage[V] | 1331.2 | |||
Voltage range[v] | 1164.8~1497.6 | |||
Charge and discharge ratio | ≤0.5CP | |||
Max.charging and | 2500 | |||
Operating | Charging[C] | 0~50 | ||
Discharging[℃] | -20~55 | |||
Recommended ambient | 25±10 | |||
Cycle life | ≥6000times | 25±10℃,P2,90%DOD,80%EOL | ||
Cooling method | Liquid cooling | Liquid cooling medium: | ||
System | BMS | Level 3 | ||
Auxiliary electrical parameter | ~40kW-400V/50Hz | ~3N+PE | ||
Fire protection system | Perfluorohexanone+ | Type S aerosol/HFC-227ea optional | ||
Anticorrosive level | C4 | |||
Lightning protection level | Level II | |||
Ingress protection | IP55 | |||
Operating temperature range [C] | -20 ~+50 | >45℃ derating | ||
Storage temperature[℃] | -20 ~+45 | <6months | ||
Operating humidity range | 0~95%RH | No condensation | ||
Installation mode | Installation mode | |||
Working condition | Max.2 charge and 2 discharge per day | |||
System communication interface | CAN/Ethernet/RS485 | |||
External system | Modbus TCP | |||
Altitude[m] | ≤3000 | |||
Dimension(D*W*H)[mm] | 6058*2438*2896 | 20 feet | ||
Weight[T] | ~41 | |||
Certificate | GB/T36276、GB/T34131 |