Availability: | |
---|---|
Quantity: | |
Smart
Cloud-based smart operation and maintenance,Al-enabled remote monitoring and early warning ensure the full life cycle of batteries,while multi-mode switching increases revenue
Safety
Smart warning ensures energy storage safety and precise temperature control extends product life by 12%.
Simple
Occupying only 2.72m of floor space,modular deployment enables rapid installation,while prefabricated components save 15%in costs.
Expansive
Hand-in-hand parallel expansion,covering a wide power range from 50kW to 300kW and a broad energy range from 107.5kWh to 300kWh.
Technical Parameters
Model | Smart 150 | |
Wind Power Input (optional) | Rated input power/Max.power | 10kW/20kW |
Rated input voltage/range | 380Vac/0~600Vac | |
Operating mode | MPPT | |
MPPT voltage range | 260~600Vac | |
Input protection | Fuse; Lightning protection circuit | |
Unloadingmode/Max.unloading current | PWM/200Adc | |
PV Input | Max.input power | 50kW |
Starting voltage | 200V | |
Max.DC inputvoltage | 1000Vdc | |
Rated DC input voltage | 630Vdc | |
MPPT voltage range | 200-850Vdc | |
Qty.Of MPPT | 4 | |
Qty.ofsingle-channel MPPT input channels | 2 | |
Max.input current | 30A*4 | |
Max.short circuit current | 40A*4 | |
Diesel Generator Input | Rated input power | 50kW |
Input voltage | 380Vac | |
Input current | 75A | |
ESS | Rated energy | 150.5 kWh |
Rated capacity | 280Ah | |
Rated voltage | 537.6Vdc | |
Battery voltage range | 470.4~604.8 Vdc | |
Rated charge/dischargecurrent | 90A | |
Max.charge/discharge current | 100A | |
Machine AC Output | Rated output voltage | 50kW |
On-grid Max.input apparent power | 50kVA | |
On-grid Max.output apparent power | 50kVA | |
Off-grid Max.output apparent power | 50kVA | |
Max.output current | 75A | |
Ratedvoltage(Input and output) | 3L/N/PE;380V | |
Grid frequency | 50Hz/60Hz | |
THDu | <3%@rated power &linear load | |
Inverter Max.efficiency | 98.4% | |
General Parameters | Weight | 3000kg |
Dimensions | 1600*1700*2591(W*D*Hmm) | |
Ingress protection | IP54 | |
Anticorrosive level | C4 | |
Communication mode | RS485,Ethernet,4G | |
Operating temperature | -30℃~55℃(45℃ derating) | |
Storage temperature | -20℃~45℃(SOC30%~50%,<6months) | |
Relative humidity | 5~95%,no condensing | |
Altitude | 3000m(>2000m derating) | |
Cooling mode | Smart air conditioner &fan |